표 4. | Table 4. S1 EMP 발생기에 노출된 PLC 동작상태 | PLC operation characteristics of S1 EMP generator exposure
Power[kV/m]/Distance[m]
LED flicker circuit
Charge/discharge circuit
RS485 cable induced voltage[V]
20 / 10
Normal
After malfunction, automatic return (Temporary upset)
68.8
40 / 5
Off
After malfunction, automatic return (Temporary upset)
86.2